On-grid side Parallel connection of Multi Triphase Hybrid Inverters

1. Preparation: Accessories​

Note: 

  • We advise to use 1.5mm² CT connection line.​
  • CAN communication wire between inverters and the wire between inverter and datalogger,  you are advised to use a DJYP2VP2-22 2x2x1 PC cable or a communications cable with a conductor cross-sectional area of 1 mm².​
  • CT Rated current ratio: XXX/5A. Accuracy requirement: 0.5%. ​
  • Due to the different diameters of the access power bus, it’s recommended to purchase CT locally.​

 

2.1 Installation Wiring​: Overview Map​

 

2.2 Installation Wiring​: CT Installation​

The CT is installed on the L wire of the access power bus. ​

 

2.3 Installation Wiring​: CTs & Meter Connection​

 

2.4 Installation Wiring​: Meter & Datalogger Connection​

 

2.5 Installation Wiring​: CAN Connection​

Connect the RS485 cable to the Com2 port of the inverter as shown in the figure below and tighten the waterproof nut and the communication interface cover.​

 

3.1 Settings​: Datalogger Configuration​

The datalogger is connected with laptop directly. ​

 

3.2 Settings​

Step 1: Change computer network adapter settings.​ (With a network cable, connect the laptop and the datalogger)​

  1. Open network & internet settings.​
  2. Click ‘Ethernet’ in the network & internet list.​
  3. Double click ethernet icon.​
  4. Find IP settings and click ‘Edit’.​
  5. Choose ‘Manual’ on the Edit IP setting page and open IPv4 edit button.​
  6. Finally, enter the information as shown.

 

3.3 Settings​: Configuration Datalogger​ on the Sunways Website 

  1. Open the browser, enter URL 10.10.100.254 ​
  2. Fill in the account ‘admin’ and the default password ‘admin12’.​

All datalogger information is shown on overview page. ​

 

Step 2: Configure the datalogger WIFI​

  1. Search for the WIFI name “ WIFI-AP********”, which released by the datalogger and connect to the hotspot.​

  2. Open the URL 10.10.100.254, and input username and password “admin”.​

  3. Click “STA Setting”, then click “Scan”, you can find the router WIFI signal.​

       (Note: Only support 2.412GHZ-2.484GHZ router)​

  1. Finally, input the password in the blank and click “Save”. If the WIFI connection is successful, the indicator on the datalogger will be always on.​